It is suitable for all power generation, distribution, and consumption sites, performing functions such as 380V/220V power collection and distribution, system monitoring and protection, and control and protection of electrical facilities and equipment in the power systems of power plants, substations, industrial and mining enterprises, hotels, ports, and other end-users.


Category:

Low-Voltage Switchgear

Keywords:

GCS Low-Voltage Switchgear



Detailed Introduction Technical Specifications

GCS The low-voltage withdrawable switchgear (hereinafter referred to as the “switchgear”) was jointly designed and developed by a joint design team from the Ministry of Electric Power and the Ministry of Machinery Industry in response to the requirements of industry authorities, a broad base of power users, and design institutes. It is tailored to China’s national conditions, features high technical performance indicators, meets the needs of power market development, and is capable of competing with currently imported products. In July 1996, this switchgear passed a joint appraisal conducted by the two ministries in Shanghai and has since been highly regarded and positively endorsed by power utility departments.

The Ministry of Electric Power and the Ministry of Machinery Industry jointly issued [for safe use] 1997 】 01 Number, aircraft weight [ 1997 】 01 The official document has been issued, “Regarding” GCS “Notice on Issues Related to the Promotion and Application of Type Low-Voltage Withdrawable Switchgear.” At present, GCS Low-voltage withdrawable switchgear has been widely adopted by power users.

This switchgear complies with IEC 61439-2 Low-Voltage Switchgear and Control Gear Assemblies - The nth 2 Section: Power Switchgear and Control Equipment, GB 7251.12 Low-Voltage Switchgear and Control Gear Assemblies - The nth 2 Section: Complete Sets of Power Switchgear and Control Equipment, GB/T 24274-2009 Standards such as “Low-Voltage Withdrawable Switchgear and Control Equipment.”

This switchgear is suitable for power distribution systems in industries such as power plants, petroleum, chemical engineering, metallurgy, textiles, and high-rise buildings. In highly automated facilities like large power plants and petrochemical complexes that require interface with computers, it serves as a three-phase AC system with a frequency of 50 ( 60 ) Hertz , the rated operating voltage is 380V ( 400V )、 690V , with a rated current of 4000A Low-voltage complete switchgear used for distribution, centralized motor control, and reactive power compensation in power generation and supply systems of 1 kV and below.

3.1 The maximum ambient air temperature is +40℃ , the lower limit is -5°C , and 24 The average temperature within the hour shall not exceed +35°C , if the duration is exceeded, operation at a reduced capacity shall be implemented based on the actual situation.

3.2 Air is clean, with relative humidity at the highest temperature. +40℃ At the time, no more than 50% At lower temperatures, higher relative humidity is permissible, for example: +20°C At the time of 90% However, the potential impact of condensation caused by temperature fluctuations should be taken into account.

3.3 The tilt during equipment installation shall not exceed 5 degree. The elevation of the place of use shall not exceed 2000m.

3.4 In media that pose no explosion hazard and contain no gases or conductive dust capable of corroding metals or damaging insulation.

3.5 If users have any special requirements, they may negotiate with our company to find a solution.

 

Name Unit Parameters
Rated voltage of the main circuit V AC 380 (400), 690
Rated Voltage of Auxiliary Circuit V AC 220, 380 (400)
DC 110, 220
Rated frequency Hertz 50(60)
Rated Insulation Voltage V 690, 800
Rated current Horizontal busbar A ≤4000
Vertical busbar A Up to 1,000
Busbar rated short-time withstand current kA1s 10, 20, 50, 80
Busbar Rated Peak Withstand Current kA1s 17, 40, 105, 176
Power-frequency test voltage for 1 minute Main Circuit V 1890
Busbar Three-phase four-wire system  A.B.C.PEN
Three-phase five-wire system  A.B.C.PE.N
Protection Level   IP30, IP40, IP42