GCK Series Low-Voltage Withdrawable Switchgear


Category:

Low-Voltage Switchgear

Keywords:

GCK Series Low-Voltage Withdrawable Switchgear



Detailed Introduction Technical Specifications

Usage:

The GCK low-voltage withdrawable switchgear (hereinafter referred to as the switchgear) is a new product developed by our company through the assimilation and application of advanced technologies from comparable international products. It is suitable for three-phase AC power systems with frequencies of 50 Hz and 60 Hz, rated voltages up to 660 V, and rated currents of 5,000 A or less, whether configured as three-phase four-wire or three-phase five-wire systems. The switchgear is used in power generation plants, substations, industrial and mining enterprises, commercial buildings, hotels, airports, ports, and other electrical users and power systems for receiving and distributing electrical energy.

This product complies with the international standard IEC 60439 and the national standard GB 7251.1. It features high breaking capacity, excellent dynamic and thermal stability, a novel and well‑designed structure, a comprehensive electrical scheme, strong series compatibility, broad applicability, and a high degree of protection—making it an ideal replacement for older models. Its technical performance has reached the current international standard.

 

Structural features:

1. The equipment is compact, accommodating multiple functional units within a small footprint.

2. Highly versatile structure and flexible assembly: The frame is constructed by assembling FA‑type steel or C‑section profiles in a 20 mm modular system, meeting the requirements of various structural configurations.

3. Adopts a standardized modular design: components can be assembled into standard units for protection, operation, switching, control, regulation, measurement, and indication, allowing users to select and configure them as needed to create frame structures and drawer units with various configurations.

4. Safe and Reliable: All structural components inside the cabinet are treated with galvanizing and passivation. The door panels and side panels around the cabinet frame are finished with electrostatic powder coating, providing both robust mechanical strength and dependable insulation protection.

5. High technical performance: Key parameters meet contemporary international advanced standards.

6. Easy to disassemble and assemble: No special or complex tools required.

 

Normal operating conditions:

1. The maximum ambient air temperature is +40°C, and the minimum is -5°C. Furthermore, the average temperature over a 24-hour period shall not exceed +35°C.

2. The air shall be clean, with a relative humidity not exceeding 50% at the maximum temperature of 40°C. At lower temperatures, higher relative humidities are permissible (e.g., 90% at +20°C), but it should be taken into account that temperature fluctuations may occasionally lead to condensation.

3. During equipment installation, the vertical deviation shall not exceed 5 degrees, and the installation site altitude shall not exceed 2,000 m.

4. The equipment shall be installed in an environment free from explosive hazards, with no corrosive gases or conductive dust that could damage the insulation. For installations that do not meet the above‑mentioned normal operating conditions or that require special operating conditions, users shall consult with our company.

 

GCK Basic Electrical Parameters
1 Rated Insulation Voltage AC660V, AC1000V
2 Rated operating voltage AC380V, AC660V
3 Rated current of the horizontal busbar 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A
4 Rated current of the vertical busbar 1000A
5 Maximum current of the power supply circuit 4000A
6 Maximum current of the drawer circuit 800A
7 Maximum motor capacity control 320kW
8 Peak withstand current of the horizontal busbar [0.1 s] 63kA,105kA,176kA,220kA
9 Short-time withstand current of the horizontal busbar [1 s] 30kA, 50kA, 80kA, 100kA
10 Peak withstand current of the vertical busbar [0.1 s] 63kA,105kA
11 Short-time withstand current of the vertical busbar [1 s] 30kA,50kA
12 Rated Power-Frequency Withstand Voltage [1 min] 2500V
13 Secondary power-frequency withstand voltage [1 min] 2500V
14 *Enclosure protection rating IP30, IP40, IP42
15 Housing dimensions Width 600 [800, 1000] × Depth 800 [1000] × Height 2200