ZGS-Z(H)/12 Combined Transformer
The ZGS-Z(H)/12 modular transformer (American-style pad-mounted substation) is a series of products independently developed by Tian’an Electric after assimilating advanced foreign technologies. It is designed for 10/0.4 kV, 50 Hz distribution systems, with rated capacities ranging from 50 to 1,600 kVA.
Category:
Box-type substation
Keywords:
ZGS-Z(H)/12 Combined Transformer
The ZGS-Z(H)/12 modular transformer (American-style pad-mounted substation) is a series of products independently developed by Tian’an Electric through the digestion and absorption of advanced foreign technologies. It is designed for 10/0.4 kV, 50 Hz distribution systems, with a rated capacity ranging from 50 to 1,600 kVA. This product integrates the transformer core, high-voltage load switch, fuses, and other components within a single oil-filled tank, using the transformer’s insulating oil as both the insulation medium and the cooling medium for the entire assembly. It features a compact structure, small footprint, convenient and flexible installation, and an aesthetically pleasing appearance.
Scope of application: urban public distribution systems, urban street lighting substations, and temporary power supply for construction sites.
1) Fully insulated and fully sealed design, ensuring safety, reliability, and maintenance-free operation, with dependable protection of personal safety;
2) The high-voltage side is protected by a dual-fuse system, with the plug-in fuse incorporating both temperature and current sensitivity, and the backup fuse being a current-limiting type, thereby reducing operating costs.
3) The high-voltage incoming line employs a cable connector assembly, offering full insulation, safety and reliability, and convenient operation.
4) It can be used in both ring networks and terminal applications, with seamless switching that enhances power supply reliability.
5) The transformer adopts a three-phase three-limb or three-phase five-limb core structure, with either a stepped-joint core assembly process or a wound-core process, resulting in low noise, low losses, and strong short-circuit and overload withstand capabilities.
6) Special processes of vacuum drying and vacuum oil impregnation are employed;
7) The enclosure may be designed for corrosion resistance and subjected to special paint coating in accordance with the requirements of the operating environment.
Product Technical Specifications and Physical Dimensions
| Serial Number | Name | Unit | Parameters |
| 1 | Rated voltage | kilovolt | 12 |
| 2 | Rated current | A | 630 |
| 3 | Rated frequency | Hertz | 50 |
| 4 | Rated breaking current | A | 630 |
| 5 | Thermal stability current | kA | February 16 |
| 6 | Dynamic stability current | kA | 40 |
| 7 | Number of full-load breaking operations | next | 20 |
| 8 | Mechanical life | next | 2000 |
| 9 | 1-minute power-frequency withstand voltage (phase-to-phase and phase-to-ground) | kilovolt | 42 |
| 10 | Lightning Impulse Level (Phase-to-Phase and Phase-to-Ground) | kilovolt | 75 |
High-Voltage Cable Connector Parameters
| Serial Number | Name | Unit | Parameters |
| 1 | Rated voltage | kilovolt | 12 |
| 2 | Rated current | A | 200, 300, 630 |
| 3 | 1-minute power-frequency withstand voltage | kilovolt | 42 |
| 4 | Insulation resistance | MΩ | 2000 |
| 5 | Contact resistance | microohm | ≤100 |
Fuse Parameters
Back-up current-limiting fuses and plug-in fuses are oil-immersed.
| Rated Capacity (kVA) | Rated voltage: 6 kV | Rated voltage: 10 kV | ||
| Current-limiting fuse (A) | Plug-in fuse model | Current-limiting fuse (A) | Plug-in fuse model | |
| 50 | 40 | 12 | 40 | 6 |
| 100 | 50 | 15 | 40 | 12 |
| 160 | 80 | 25 | 50 | 15 |
| 200 | 80 | 25 | 80 | 25 |
| 250 | 125 | 25 | 80 | 25 |
| 315 | 150 | 50 | 80 | 25 |
| 400 | 150 | 50 | 100 | 40 |
| 500 | 175 | 65 | 125 | 50 |
| 630 | 175 | 100 | 150 | 50 |
| 800 | 200 | 100 | 150 | 65 |
| 1000 | 200 | 140 | 200 | 100 |
| 1250 | 200 | 200 | 200 | 100 |
Transformer Technical Parameters
| Rated capacity (kVA) | No-load loss (W) | Load loss (W) | Impedance Voltage | ||
| S13 | S11 | S13 | S11 | ||
| 50 | 100 | 130 | 910/870 | 910/870 | 4 |
| 100 | 150 | 200 | 1580/1500 | 1580/1500 | |
| 160 | 200 | 280 | 2310/2200 | 2310/2200 | |
| 200 | 240 | 340 | 2730/2600 | 2730/2600 | |
| 250 | 290 | 400 | 3200/3050 | 3200/3050 | |
| 315 | 340 | 480 | 3830/3650 | 3830/3650 | |
| 400 | 410 | 570 | 4520/4300 | 4520/4300 | |
| 500 | 480 | 680 | 5410/5150 | 5410/5150 | |
| 630 | 570 | 810 | 6200 | 6200 | 4.5 |
| 800 | 700 | 980 | 7500 | 7500 | |
| 1000 | 830 | 1150 | 10300 | 10300 | |
| 1250 | 970 | 1360 | 12000 | 12000 | |
Consult now