ZGS-Z/35 Combined Transformer for Wind Power Generation
The ZGS-ZF series of wind-power-specific combined transformers is a product line independently developed by Tian’an Electric to meet the needs of wind-power generation projects both domestically and internationally. Among domestic manufacturers of similar products, Tian’an Electric was among the earliest to conduct R&D, commence production, and put these transformers into operation.
Category:
Box-type substation
Keywords:
ZGS-Z/35 Combined Transformer for Wind Power Generation
The ZGS-ZF series of wind-power-specific combined transformers is a product line independently developed by Tian’an Electric to meet the needs of wind-power generation projects both domestically and internationally. Among domestic manufacturers of similar products, Tian’an Electric was among the earliest to conduct R&D, commence production, and put these transformers into operation.
The ZGS-Z.F-□/35 series combined transformer for wind power generation is a specialized power equipment that integrates a step-up transformer, high-voltage current-limiting fuse, load switch, low-voltage switch, and associated auxiliary equipment into a single unit. It steps up the 0.69 kV voltage generated by the wind turbine generator set to 35 kV and then transmits the electrical energy via a 35 kV cable line. It is the ideal matching equipment for wind power generation systems.
The ZGS-Z.F-□/35 series combined transformer is designed for 50 Hz, 35/0.69 kV wind power generation systems, with a rated capacity ranging from 800 to 2,350 kVA, and is specifically intended for power supply and distribution in wind farms.
1) Conducted a 4,000-meter high-altitude test;
2) The main heating element (the transformer itself) is installed outdoors, while all other electrical equipment is housed in a metal enclosure with an IP54 protection rating.
3) Compact and miniaturized design: for products with the same capacity (below 1600 kV), the footprint is only 52% of that of a European-style pad-mounted substation.
4) Rain- and snow-proof, sand- and dust-proof, corrosion-resistant, and fully enclosed, ensuring suitability for long-term outdoor use;
5) We can undertake the non-standard design and manufacturing of equipment in various capacities as required by the design institute.
Load Switch Parameter Table
| Serial Number | Name | Unit | Parameters | |
| 1 | Rated voltage | kilovolt | 40.5 | |
| 2 | Rated current | A | 315 | 630 |
| 3 | Rated frequency | Hertz | 50 | |
| 4 | Rated short-circuit withstand current | kA/2s | 12.5 | 20 |
| 5 | Rated Peak Withstand Current | kA | 31.5 | 50 |
| 6 | Mechanical life | next | 2000 | |
| 7 | 1-minute power-frequency withstand voltage (phase-to-phase and phase-to-ground) | kilovolt | 95 | |
| 8 | Lightning Impulse Level (Phase-to-Phase and Phase-to-Ground) | kilovolt | 185 | |
Fuse Parameter Table
| Rated voltage | Fuse rated current A | Rated current of the fuse element, A | Rated maximum breaking current kA |
| 40.5 | 40 | 20, 25, 31.5, 40, 50, 63 | 31.5 |
Surge Arrester Parameter Table
| Rated voltage | Continuous Operating Voltage | DC Reference Voltage (1 mA) | Nominal discharge current | Rated discharge current residual voltage | 2 ms square-wave current Tolerance value |
| 51kV | 40.8kV | ≥73kV | 5 kA (peak) | ≤134 kV (peak) | ≥250A (peak) |
Main Technical Parameters Table for Transformers
| Rated capacity (Kilovolt-Amperes) | No-load loss (W) | Load Loss (W) | No-load loss (%) | Impedance Voltage (%) | ||
| S9 type | S11 type | S9 type | S11 type | |||
| 800 | 1230 | 975 | 9900 | 9350 | 0.8 | 6.5 |
| 900 | 1350 | 1065 | 10820 | 10600 | 0.8 | 6.5 |
| 1000 | 1440 | 1155 | 12150 | 11480 | 0.75 | 6.5 |
| 1350 | 1870 | 1450 | 15540 | 14380 | 0.7 | 6.5 |
| 1600 | 2120 | 1660 | 17550 | 16580 | 0.65 | 6.5 |
| 2350 | 2830 | 2290 | 23420 | 22220 | 0.6 | 6.5 |
Consult now