  • ZGS-ZF-35风电专用组合式变压器png.jpg

ZGS-Z/35 Combined Transformer for Wind Power Generation

The ZGS-ZF series of wind-power-specific combined transformers is a product line independently developed by Tian’an Electric to meet the needs of wind-power generation projects both domestically and internationally. Among domestic manufacturers of similar products, Tian’an Electric was among the earliest to conduct R&D, commence production, and put these transformers into operation.


Category:

Box-type substation

Keywords:

ZGS-Z/35 Combined Transformer for Wind Power Generation



Detailed Introduction Technical Specifications

The ZGS-ZF series of wind-power-specific combined transformers is a product line independently developed by Tian’an Electric to meet the needs of wind-power generation projects both domestically and internationally. Among domestic manufacturers of similar products, Tian’an Electric was among the earliest to conduct R&D, commence production, and put these transformers into operation.

The ZGS-Z.F-□/35 series combined transformer for wind power generation is a specialized power equipment that integrates a step-up transformer, high-voltage current-limiting fuse, load switch, low-voltage switch, and associated auxiliary equipment into a single unit. It steps up the 0.69 kV voltage generated by the wind turbine generator set to 35 kV and then transmits the electrical energy via a 35 kV cable line. It is the ideal matching equipment for wind power generation systems.

The ZGS-Z.F-□/35 series combined transformer is designed for 50 Hz, 35/0.69 kV wind power generation systems, with a rated capacity ranging from 800 to 2,350 kVA, and is specifically intended for power supply and distribution in wind farms.

1) Conducted a 4,000-meter high-altitude test; 
2) The main heating element (the transformer itself) is installed outdoors, while all other electrical equipment is housed in a metal enclosure with an IP54 protection rating. 
3) Compact and miniaturized design: for products with the same capacity (below 1600 kV), the footprint is only 52% of that of a European-style pad-mounted substation. 
4) Rain- and snow-proof, sand- and dust-proof, corrosion-resistant, and fully enclosed, ensuring suitability for long-term outdoor use; 
5) We can undertake the non-standard design and manufacturing of equipment in various capacities as required by the design institute.

 

Load Switch Parameter Table

Serial NumberNameUnitParameters
1Rated voltagekilovolt40.5
2Rated currentA315630
3Rated frequencyHertz50
4Rated short-circuit withstand currentkA/2s12.520
5Rated Peak Withstand CurrentkA31.550
6Mechanical lifenext2000
71-minute power-frequency withstand voltage (phase-to-phase and phase-to-ground)kilovolt95
8Lightning Impulse Level (Phase-to-Phase and Phase-to-Ground)kilovolt185

Fuse Parameter Table

Rated voltageFuse rated current ARated current of the fuse element, ARated maximum breaking current kA
40.54020, 25, 31.5, 40, 50, 6331.5

Surge Arrester Parameter Table

Rated voltageContinuous Operating VoltageDC Reference Voltage (1 mA)Nominal discharge currentRated discharge current residual voltage2 ms square-wave current 
Tolerance value
51kV40.8kV≥73kV5 kA (peak)≤134 kV (peak)≥250A (peak)

Main Technical Parameters Table for Transformers

Rated capacity 
(Kilovolt-Amperes)
No-load loss (W)Load Loss (W)No-load loss 
(%)
Impedance Voltage 
(%)
S9 typeS11 typeS9 typeS11 type
8001230975990093500.86.5
9001350106510820106000.86.5
10001440115512150114800.756.5
13501870145015540143800.76.5
16002120166017550165800.656.5
23502830229023420222200.66.5

Consult now

Submit a message
Consult now