YBT12-24 Series Combined Substation
Category:
Box-type substation
Keywords:
YBT12-24 Series Combined Substation
The TANK1 series (intelligent type) universal vacuum circuit breaker (hereinafter referred to as the “circuit breaker”) is suitable for AC distribution networks with a frequency of 50 Hz, rated voltages of 400 V and 690 V, and rated currents ranging from 630 A to 2,000 A (the four-pole version is applicable to three-phase four-wire or three-phase five-wire systems). It is used for power distribution and for protecting circuits and power supply equipment against faults such as overloads, undervoltage, short circuits, and single-phase-to-ground faults.
The circuit breaker complies with standards such as GB 14048.2-2001 “Low-Voltage Switchgear and Controlgear—Low-Voltage Circuit Breakers” and IEC 60947-2 “Low-Voltage Switchgear and Controlgear—Low-Voltage Circuit Breakers.”
Features:
- High breaking capacity and strong arc-extinguishing capability, truly achieving zero arcing.
- It is particularly suitable for applications where air circuit breakers are either unsuitable or impractical, such as wind power generation, coal mining, chemical processing, and metallurgy.
- Circuit breakers are available in two structural configurations: fixed-type and drawer-type.
- Mechanical interlocks can be implemented in either the vertical or horizontal direction.
- It is interchangeable with the DW45-2000 main body designed by the Shanghai Institute of Scientific Research.
- The intelligent trip unit features four-stage protection with precise selective coordination.
- It can be equipped with an open communication interface and features four remote functions to meet the requirements of distribution automation systems.
- Passed the low-temperature resistance test at –40°C.
- Depending on the ambient air temperature, the intelligent trip unit can be selected as either digital or LCD type.
- Certified under the 3C standard and holding national patent technology.
| Project | Unit | Parameters | |
| High-voltage unit | Rated voltage | KV | 24 |
| Rated frequency | Hertz | 50 | |
| Rated current of the main busbar | A | 630 | |
| 1-minute power-frequency withstand voltage to ground and between phases/isolation breaks | kilovolt | 50/65 | |
| Lightning impulse withstand voltage to ground and between phases/isolation breaks | kilovolt | 95/110 | |
| Rated short-time withstand current | kA/s | February 25 | |
| Rated Peak Withstand Current | kA | 63 | |
| Rated short-time making current | kA | 63 | |
| Fuse breaking current | kA | 31.5 | |
| Circuit breaker breaking current | kA | 25 | |
| Low-voltage unit | Rated voltage | V | 400 |
| Rated current of the main circuit | A | 100~4000 | |
| Rated Ultimate Short-Circuit Breaking Capacity | kA | 80 | |
| Rated short-circuit breaking capacity | kA | 50(65) | |
| Rated short-time withstand current | kA/1s | 50(65) | |
| Branch current, compensation capacity | As per user request | ||
| Transformer Unit | Rated capacity | KVA | 30~2000 |
| Impedance Voltage | % | 4 4.5 | |
| Tap range | % | ±2×2.5 ±5 | |
| Connection Group | Y,yn0 D,yn11 | ||
| Box body | Enclosure Protection Rating | IP23 | |
| Sound level | decibel | ≤50 |