GW5-126D Outdoor AC High-Voltage Isolating Switch
The GW5 (GT10)-126D/1600-40 outdoor AC high-voltage disconnector is a major improvement over the GW5-126 model manufactured by other companies, addressing such shortcomings as excessive operating force, tooth breakage in the bevel gears, severe corrosion of metallic materials, and loss of control over the open-position. It is a mature product that Tian’an recommends for high-voltage distribution networks.
Category:
High-voltage switchgear
Keywords:
GW5-126D Outdoor AC High-Voltage Isolating Switch
The GW5 (GT10)-126D/1600-40 outdoor AC high-voltage disconnector is a major improvement over the GW5-126 model manufactured by other companies, addressing such shortcomings as excessive operating force, tooth breakage in the bevel gears, severe corrosion of metallic materials, and loss of control over the open-position. It is a mature product that Tian’an recommends for high-voltage distribution networks.
The GW5 (GT10)-126D/1600-40 horizontal single-break outdoor AC high-voltage isolating switch is suitable for power systems with an AC frequency of 50 Hz and a rated voltage of 110 kV. It is used to connect and disconnect high-voltage lines under no-load conditions, as well as to electrically isolate high-voltage busbars, circuit breakers, and other electrical equipment under maintenance from energized high-voltage lines. It can also be used to switch small capacitive or inductive currents.
Adopts a dual-column horizontal rotary structure;
Simple structure, aesthetically pleasing appearance, flexible and versatile installation options, and convenient operation, inspection, and maintenance.
The operating mechanism is simple, requires minimal operating force, and provides self-locking and interlocking when the switch is fully closed or open, thereby preventing inadvertent operation of the isolating switch due to external forces.
The main switch may be equipped with an electric operating mechanism;
The entire current circuit is constructed from silver-plated pure copper components, with a special lubricating protective coating (electronic oil) applied to the surface, which significantly slows down the oxidation of the silver layer and ensures that the switch maintains excellent conductivity even after prolonged outdoor operation.
Excellent corrosion resistance: Utilizes materials such as stainless steel, aluminum alloy, and copper alloy, and employs a variety of anti-corrosion measures, including Dacromet coating, hot-dip galvanizing, nickel-phosphorus alloy composite plating, and paint spraying.
The isolating switch and earthing switch are mechanically interlocked between the two lock plates within the drive box, ensuring safety and reliability.
Serial Number | Name | Unit | Parameters | |
1 | Rated voltage | kilovolt | 126 | |
2 | Rated current | A | 630/1250/1600 | |
3 | Rated peak withstand current of isolating switches and earthing switches | kA | 80/100 | |
4 | 3-second rated short-time withstand current for isolating switches and earthing switches | kA | 31.5/40 | |
5 | Mechanical life of isolating switches and earthing switches | next | 2,000 each | |
6 | Main Circuit Resistance of Isolating Switch | microohm | ≤75 | |
7 | Rated 1-min power-frequency withstand voltage | Phase-to-phase, phase-to-ground (dry/wet) | kilovolt | 230 |
| Isolation fracture | kilovolt | 265 | ||
8 | Rated Lightning Impulse Withstand Voltage | Phase-to-phase, phase-to-ground | kilovolt | 550 |
| Isolation fracture | kilovolt | 630 | ||
9 | Terminal block Rated Static Tensile Force | Vertical Static Tensile Force FthA | N | 750 |
| Horizontal Static Tensile Force FthB | N | 250 | ||
10 | Insulation clearance of the main disconnect switch contacts | mm | ≥1000 | |
11 | Phase-to-phase center distance | mm | ≥2000 | |
12 | Phase-to-phase insulation distance | mm | ≥1000 | |
13 | Clamping force of the main isolator’s moving contact blade | N | ≥140±30 | |
14 | Closing synchronism error of the main isolating switch | mm | ≤12 | |
Consult now