GW4-126D Outdoor AC High-Voltage Isolating Switch

The GW4-126D double-column horizontal outdoor AC high-voltage disconnector is suitable for power systems with a frequency of 50 Hz and a rated voltage of 110 kV. It is used to switch high-voltage lines under no-load conditions and to provide electrical isolation between high-voltage busbars, circuit breakers, and other electrical equipment under maintenance and energized high-voltage lines, thereby ensuring that the equipment under maintenance and the maintenance personnel are provided with a visible insulation clearance that meets the required specifications.


Category:

High-voltage switchgear

Keywords:

GW4-126D Outdoor AC High-Voltage Isolating Switch



Detailed Introduction Technical Specifications

The GW4-126D double-column horizontal outdoor AC high-voltage disconnector is suitable for power systems with a frequency of 50 Hz and a rated voltage of 110 kV. It is used to switch high-voltage lines under no-load conditions and to provide electrical isolation between high-voltage busbars, circuit breakers, and other electrical equipment under maintenance and energized high-voltage lines, thereby ensuring that the equipment under maintenance and the maintenance personnel are provided with a visible insulation clearance that meets the required standards.

 

Adopts a dual-column horizontal rotary structure;

Simple structure, easy commissioning, and aesthetically pleasing design;

The isolating switch can be operated as a single pole or, via interphase linkages, as a three-pole coordinated operation.

It features both electric and manual operation modes;

Features dual mechanical and electrical interlocks;

The components are predominantly made of aluminum alloy and undergo special anti-corrosion treatment, providing excellent outdoor corrosion resistance.

The conductive contact areas are silver-plated, and an anti-oxidation coating is applied to the silver-plated surface to prevent oxidation of the switch.

Serial Number

Name

Unit

Parameters

1

Rated voltage

kilovolt

126

2

Rated current

A

630/1250/1600/2000

3

Peak withstand current of isolating switches and earthing switches

kA

63/80/100

4

Short-time withstand current of isolating switches and earthing switches for 3 seconds

kA

25/31.5/40

5

Rated 1-min power-frequency withstand voltage

kilovolt

230/265

6

Rated Lightning Impulse Withstand Voltage

kilovolt

550/630

7

Closing and opening time

s

8±1

8

Control voltage

V

AC220

9

Phase-to-phase center distance

mm

≥2000

10

Phase-to-phase insulation distance

mm

≥1000

11

Disconnector contact gap

mm

≥1050

12

Ground switch break distance

mm

≥1000

13

Insulation clearance between the conductive part and ground

mm

≥910

14

Out-of-phase closing and opening of the three phases of the isolating switch

mm

≤12

15

Out-of-phase closing and opening of the three phases of the earthing switch

mm

≤15