LW39-126 Outdoor AC High-Voltage SF6 Circuit Breaker
The LW39-126 outdoor AC high-voltage porcelain post-type SF6 circuit breaker is suitable for power systems with a frequency of 50 Hz and a nominal system voltage of 110 kV, and serves as a primary electrical device for control and protection in power plants and substations.
Category:
High-voltage switchgear
Keywords:
LW39-126 Outdoor AC High-Voltage SF6 Circuit Breaker
The LW39-126 outdoor AC high-voltage porcelain-post SF6 circuit breaker is suitable for power systems with a frequency of 50 Hz and a nominal system voltage of 110 kV, serving as a primary electrical device for control and protection in power plants and substations. The circuit breaker employs the thermally expanded self-blowing arc-extinguishing principle and is internally filled with SF6 gas, which exhibits excellent arc-extinguishing and electrical insulation properties. All seals utilize double-ring O-rings to effectively prevent gas leakage, and it is equipped with a CT30-type spring-operated mechanism to achieve three-phase mechanical interlocking operation.
It exhibits stable breaking performance and can reliably interrupt faults such as outgoing-line short circuits, out-of-step conditions, and near-zone faults.
The arc-extinguishing chamber features a simple and reliable structure and is easy to maintain.
Long electrical life, with the capability of making and breaking at full rated current up to 20 times, and requiring no maintenance for 10 years under normal operating conditions.
Low operating force, featuring a simple, reliable, and compact spring-operated mechanism;
The gas has a low rated filling pressure, making it suitable for low-temperature conditions;
Small footprint;
Low noise levels, suitable for residential areas;
Long maintenance intervals and minimal maintenance workload;
Short on-site installation and commissioning time.
Serial Number | Name | Unit | Parameters | |||||
1 | System Nominal Voltage | kilovolt | 110 | |||||
2 | Rated voltage | kilovolt | 126 | |||||
3 | Rated frequency | Hertz | 50/60 | |||||
4 | Rated current | A | 3150 | |||||
5 | Rated short-circuit breaking current | kA | 31.5 | 40 | ||||
6 | Rated Short-Circuit Making Current (Peak) | kA | 80 | 100 | ||||
7 | Rated short-time withstand current (thermal stability current) | kA | 31.5 | 40 | ||||
8 | Rated peak withstand current (dynamic stability current) | kA | 80 | 100 | ||||
9 | Rated short-circuit duration (thermal stability time) | s | 4 | 3 | ||||
10 | First-ever extreme coefficient |
| 1.5 | |||||
11 | Lightning Impulse Withstand Voltage | kilovolt | 650 | |||||
12 | 1-minute power-frequency withstand voltage | kilovolt | 275 | |||||
13 | Creepage distance to clearance | mm/kV | 25/31 | |||||
14 | Rated Operating Sequence |
| O-0.3s-CO-180s-CO | |||||
15 | Closing time | millisecond | ≤110 | |||||
16 | Breaking time | millisecond | ≤65 | |||||
17 | Combine–Separate Time | millisecond | ≤85 | |||||
18 | Closing time | millisecond | 80±5 | |||||
19 | Trip time | millisecond | 33±7 | |||||
20 | Number of断口 per pole | one | 1 | |||||
21 | Main circuit resistance | microohm | ≤45 | |||||
22 | Mechanical life | next | 10000 | |||||
23 | SF6 gas pressure (20°C) | Rated value | Mpa | 0.55 | 0.60 | |||
| Alarm value | Mpa | 0.50 | 0.55 | |||||
| Lockout value | Mpa | 0.45 | 0.50 | |||||
24 | SF6 moisture content | ppm (V/V) | ≤150 | |||||
25 | Annual SF6 leakage rate |
| ≤1% | |||||
26 | Auxiliary circuit voltage | V | AC220 | |||||
27 | Closing coil | Voltage | V | DC220 | DC110 | |||
| Electric current | A | 2 | 3.3 | |||||
28 | Trip coil | Voltage | V | DC220 | DC110 | |||
| Electric current | A | 2 | 5.8 | |||||
29 | Energy Storage Motor | Voltage | V | AC220/DC220 | ||||
| Power | W | 600 | ||||||
30 | Storage time | s | ≤15 | |||||