  • LW39-126户外交流高压SF6断路器.png

LW39-126 Outdoor AC High-Voltage SF6 Circuit Breaker

The LW39-126 outdoor AC high-voltage porcelain post-type SF6 circuit breaker is suitable for power systems with a frequency of 50 Hz and a nominal system voltage of 110 kV, and serves as a primary electrical device for control and protection in power plants and substations.


Category:

High-voltage switchgear

Keywords:

LW39-126 Outdoor AC High-Voltage SF6 Circuit Breaker



Detailed Introduction Technical Specifications

The LW39-126 outdoor AC high-voltage porcelain-post SF6 circuit breaker is suitable for power systems with a frequency of 50 Hz and a nominal system voltage of 110 kV, serving as a primary electrical device for control and protection in power plants and substations. The circuit breaker employs the thermally expanded self-blowing arc-extinguishing principle and is internally filled with SF6 gas, which exhibits excellent arc-extinguishing and electrical insulation properties. All seals utilize double-ring O-rings to effectively prevent gas leakage, and it is equipped with a CT30-type spring-operated mechanism to achieve three-phase mechanical interlocking operation.

 

It exhibits stable breaking performance and can reliably interrupt faults such as outgoing-line short circuits, out-of-step conditions, and near-zone faults.

The arc-extinguishing chamber features a simple and reliable structure and is easy to maintain.

Long electrical life, with the capability of making and breaking at full rated current up to 20 times, and requiring no maintenance for 10 years under normal operating conditions.

Low operating force, featuring a simple, reliable, and compact spring-operated mechanism;

The gas has a low rated filling pressure, making it suitable for low-temperature conditions;

Small footprint;

Low noise levels, suitable for residential areas;

Long maintenance intervals and minimal maintenance workload;

Short on-site installation and commissioning time.

Serial Number

Name

Unit

Parameters

1

System Nominal Voltage

kilovolt

110

2

Rated voltage

kilovolt

126

3

Rated frequency

Hertz

50/60

4

Rated current

A

3150

5

Rated short-circuit breaking current

kA

31.5

40

6

Rated Short-Circuit Making Current (Peak)

kA

80

100

7

Rated short-time withstand current (thermal stability current)

kA

31.5

40

8

Rated peak withstand current (dynamic stability current)

kA

80

100

9

Rated short-circuit duration (thermal stability time)

s

4

3

10

First-ever extreme coefficient

 

1.5

11

Lightning Impulse Withstand Voltage

kilovolt

650

12

1-minute power-frequency withstand voltage

kilovolt

275

13

Creepage distance to clearance

mm/kV

25/31

14

Rated Operating Sequence

 

O-0.3s-CO-180s-CO

15

Closing time

millisecond

≤110

16

Breaking time

millisecond

≤65

17

Combine–Separate Time

millisecond

≤85

18

Closing time

millisecond

80±5

19

Trip time

millisecond

33±7

20

Number of断口 per pole

one

1

21

Main circuit resistance

microohm

≤45

22

Mechanical life

next

10000

23

SF6 gas pressure (20°C)Rated value

Mpa

0.55

0.60

Alarm value

Mpa

0.50

0.55

Lockout value

Mpa

0.45

0.50

24

SF6 moisture content

ppm (V/V)

≤150

25

Annual SF6 leakage rate

 

≤1%

26

Auxiliary circuit voltage

V

AC220

27

Closing coilVoltage

V

DC220

DC110

Electric current

A

2

3.3

28

Trip coilVoltage

V

DC220

DC110

Electric current

A

2

5.8

29

Energy Storage MotorVoltage

V

AC220/DC220

Power

W

600

30

Storage time

s

≤15

Consult now