GXGT1-12 Solid-Insulated Metal-Enclosed Ring Main Unit

The GXGT1-12 (XGN108-12) solid-insulated ring main unit is the latest high-performance, environmentally friendly 12 kV ring main unit independently developed by Tian’an Electric. It combines vacuum arc extinction with solid insulation technology. All live components are fully sealed within an APG injection-molded epoxy resin enclosure, and adjacent cabinets are interconnected via plug-in solid-insulated busbars, ensuring that the entire switchgear is completely immune to external environmental influences.


Category:

Medium-Voltage Switchgear

Keywords:

GXGT1-12 Solid-Insulated Metal-Enclosed Ring Main Unit



Detailed Introduction Technical Specifications

The GXGT1-12 (XGN108-12) solid-insulated ring main unit is a high-performance, environmentally friendly 12 kV switchgear independently developed by Tian’an Electric. It combines vacuum arc extinction with solid insulation technology. All live components are fully sealed within an APG injection-molded epoxy resin enclosure, and adjacent cabinets are interconnected via plug-in solid-insulated busbars, ensuring that the entire switchgear is completely immune to external environmental influences.
The GXGT1-12 solid-insulated ring main unit comprises three basic functional units: a load switch cabinet, a combined electrical apparatus cabinet, and a circuit breaker cabinet. It is suitable for 10 kV three-phase AC 50 Hz single-busbar systems and serves as equipment for receiving and distributing electrical energy, with built-in functions for line control, protection, monitoring, and communication.

 

1) Rated current up to 1250 A; breaking capacity of 25 kA.
2) External dimensions: 400 × 750 × 1500;
3) Environmentally friendly, with no greenhouse gases such as SF6;
4) Each unit is independent and does not share a common enclosure;
5) Equipped with a grounding observation window for the three-position isolating switch;
6) A fuse-based solution is in place, and the fuse is equipped with auxiliary grounding.
7) Flexible expansion is achievable through plug-in insulated busbars.

Serial Number

Project

Unit

Technical Specifications

1

Rated current

A

630, 1250

2

Rated frequency

Hertz

50

3

Rated voltage

kilovolt

12

4

Rated power-frequency withstand voltage (phase-to-phase, phase-to-ground/breaker contacts)

kilovolt

42/48

5

Rated lightning impulse withstand voltage (phase-to-phase, phase-to-ground/breaker contact)

kilovolt

75/85

6

Rated short-circuit breaking current

kA

20, 25

7

Rated short-time withstand current (RMS value)/time

kA/s

April 20, April 25

8

Internal Arc Rating

IAC

Class A, 20 kA/0.5 s

9

Partial discharge

pC

≤20

10

Protection Level

 

Live parts sealed to IP67; cabinet body sealed to IP4X.

11

External dimensions

mm

400×860×1660