HXGT6A-12(24) Gas-Insulated Metal-Enclosed Ring Main Unit
The HXGT6A-12(24) indoor gas-insulated metal-enclosed switchgear is a next-generation ring-main unit developed in-house by Tian’an Electric, with a rated voltage of 12 kV (24 kV).
Category:
Medium-Voltage Switchgear
Keywords:
HXGT6A-12(24) Gas-Insulated Metal-Enclosed Ring Main Unit
The HXGT6A-12(24) indoor gas-insulated metal-enclosed switchgear is a next-generation ring-main unit independently developed by Tian’an Electric. It is rated for 12 kV (24 kV). Building on the company’s existing HXGT6-12 air-insulated ring-main cabinet technology, this product represents a significant upgrade and represents an outstanding achievement. It successfully passed type tests at the Xi’an National High-Voltage Electrical Apparatus Testing Center in May 2016 and has also obtained TÜV Rheinland certification.
All high-voltage live components of the product are sealed within a stainless-steel enclosure filled with SF6 gas at a low gauge pressure (0.02–0.04 MPa at 20°C, IP67), thereby protecting them from external environmental conditions such as condensation, contamination, and small animals, and enabling their use in harsh environments.
1) Through TÜV Rheinland in Germany ü V certification;
2) Conducted a 4,000-meter high-altitude test;
3) Rated current: 630 A to 1250 A;
4) The external dimensions of a single bay are 350 × 820 × 1600.
5) Fully functional, featuring three types of functional units: load switch, combined electrical apparatus, and circuit breaker;
6) The load switch adopts an arc-extinguishing grid-cooled structure, providing strong arc-extinguishing capability;
7) The operating mechanism adopts a self-designed, mature modular unit structure combined with a three-position isolation mechanism, offering strong versatility and reliability.
8) The isolation gap of the three-position isolating switch shall be visible;
9) Annual leakage rate is less than 0.1%;
10) Supports various expansion methods and enables common-box arrangement.
Serial Number | Project | Unit | Technical Specifications | |
1 | Rated current | A | 630 | 1250 |
2 | Rated frequency | Hertz | 50 | |
3 | Rated voltage | kilovolt | 12 | |
4 | Power-frequency withstand voltage | kilovolt | 42/48 | |
5 | Lightning Impulse Voltage | kilovolt | 75/85 | |
6 | Rated short-circuit breaking current | kA | 20, 25, 31.5 (combined electrical apparatus) | |
7 | Rated short-time withstand current (RMS value)/time | kA/s | April 20, February 25 | |
8 | Arc duration | s | 1 | |
9 | Inflatable Enclosure Protection Rating |
| IP 67 | |
10 | Enclosure Protection Rating |
| IP 4X | |
11 | SF6 gas rated pressure (gauge pressure at 20°C) | megapascal | 0.04 | |
12 | Minimum operating pressure of SF6 gas (gauge pressure at 20°C) | megapascal | 0.02 | |
13 | Annual SF6 gas leakage rate | %/year | ≤0.1 | |
14 | External dimensions | mm | 350×820×1600 | |