  • 25)KYN28A-12铠装中置式交流金属封闭开关设备png.jpg

KYN28A-12(24) Armored Center-mounted AC Metal-enclosed Switchgear

The KYN28A-12 indoor armored center-mounted AC metal-enclosed switchgear (hereinafter referred to as the “center-mounted cabinet”) is a complete set of power distribution equipment for 3–10 kV three-phase AC systems operating at 50 Hz, configured as single-bus or single-bus sectionalized systems.


Category:

Medium-Voltage Switchgear

Keywords:

KYN28A-12(24) Armored Center-mounted AC Metal-enclosed Switchgear



Detailed Introduction Technical Specifications

The KYN28A-12 indoor armored center-mounted AC metal-enclosed switchgear (hereinafter referred to as the “center-mounted cabinet”) is a complete set of distribution equipment for 3–10 kV three-phase AC systems at 50 Hz, configured as either a single-bus or a single-bus sectionalized system. It is primarily used in power plants, for power delivery from small and medium-sized generators, for distribution in industrial and mining enterprises and other institutions, as well as for receiving and delivering power at secondary substations in the electric utility system and for starting large high-voltage motors. The cabinet is designed to provide control, protection, and monitoring functions. It complies with standards such as IEC 298 and GB 3906, and can be equipped with vacuum circuit breakers manufactured by Tian’an Electric, including models VT19 and VS1, as well as with vacuum circuit breakers from various domestic and international manufacturers, such as VD4, VB2, 3AE, and HVX.

 

1) Vacuum arc extinction and air insulation are employed;
2) The rated current can reach 4,000 A, and the short-circuit breaking current can reach 50 kA;
3) The product can be wall-mounted and maintained from the front of the cabinet, thereby reducing the footprint.
4) The main switch can be equipped with Tianan VT19 solid-insulated pole circuit breakers, VS1 circuit breakers, as well as other high-performance circuit breakers such as VD4 and VEP.
5) Overhead or cable incoming and outgoing lines may be used;
6) The cable compartment provides ample space for installing up to nine single-core cables;

Serial Number

Project

Unit

Technical Specifications

1

Rated current

A

630–4000

2

Rated frequency

Hertz

50/60

3

Rated voltage

kilovolt

12

4

Rated Power-Frequency Withstand Voltage

kilovolt

42

5

Rated Lightning Impulse Withstand Voltage

kilovolt

75

6

Rated short-circuit breaking current

kA

20–50

7

Rated short-circuit duration

s

4

8

Protection Level

 

Cabinet IP4X, compartment IP2X

9

External dimensions 
(Cable Inlet and Outlet)

(≤1250 A/31.5 kA)

mm

650×1500×2300

10

(≤1250 A/40 kA)

mm

800×1500×2300

11

(Rated current ≥ 1600 A)

mm

1000×1500×2300

12

External dimensions

Overhead incoming and outgoing lines

mm

(650–1000)×1600×2300