  • XGN49-40.5(24)气体绝缘金属封闭开关设备(C-GIS).png

XGN49-40.5(24) Gas-Insulated Metal-Enclosed Switchgear (C-GIS)

The XGN49 series indoor gas-insulated metal-enclosed switchgear (C-GIS), hereinafter referred to as the XGN49-40.5(24) gas-insulated cabinet, is a high-tech product independently developed by Tian’an Electric. It employs vacuum arc extinction and SF6 gas insulation technologies, with technical performance that ranks among the leading domestic standards and reaches an internationally advanced level.


Category:

Medium-Voltage Switchgear

Keywords:

XGN49-40.5(24) Gas-Insulated Metal-Enclosed Switchgear (C-GIS)



Detailed Introduction Technical Specifications

The XGN49 series indoor gas-insulated metal-enclosed switchgear (C-GIS), hereinafter referred to as the XGN49-40.5(24) gas-insulated cabinet, is a high-tech product independently developed by Tian’an Electric. It employs vacuum arc extinction and SF6 gas insulation technologies, with technical performance that ranks among the leading domestic standards and reaches an internationally advanced level.
All high-voltage live components of the XGN49 gas-insulated switchgear are sealed within a stainless-steel enclosure filled with SF6 gas at a low gauge pressure of 0.03 to 0.05 MPa (at 20°C), achieving an IP67 protection rating. The main switch is a spring-operated vacuum circuit breaker, complemented by a three-position isolating earthing switch. The equipment exhibits stable insulation performance and is particularly well suited for harsh environments such as high altitudes, extreme cold, high humidity, and polluted conditions. Moreover, its compact footprint makes it ideal for space-constrained applications, including rail transit systems.

 

1) Rated current up to 3,150 A; short-circuit breaking current of 31.5 kA.
2) External dimensions: 600 × 1400 × 2500 mm;
3) Vacuum arc extinction and SF6 gas insulation are employed;
4) Conducting high-altitude tests at 5,000 meters;
5) The three-position isolating switch features a visible break.
6) The product is easy and quick to install, with no need for on-site inflation.
7) Overhead outgoing lines using tubular busbars may be employed;
8) A dual-busbar technical solution can be implemented.

Serial Number

Project

Unit

Technical Specifications

1

Rated current

A

630–3150

2

Rated frequency

Hertz

50/60

3

Rated voltage

kilovolt

40.5 (24)

4

Rated Power-Frequency Withstand Voltage

kilovolt

95

5

Rated Lightning Impulse Withstand Voltage

kilovolt

185

6

Rated short-circuit breaking current

kA

20–31.5

7

Rated short-time withstand current (RMS value)/time

kA/s

April 20 to April 31.5

8

Inflatable Enclosure Protection Rating

IP

67

9

Enclosure Protection Rating

IP

4X

10

Rated operating pressure of SF6 gas (gauge pressure at 20°C)

megapascal

0.05

11

Minimum operating pressure of SF6 gas (gauge pressure at 20°C)

megapascal

0.03

12

Annual SF6 gas leakage rate

%/year

≤0.5

13

External dimensions (630 A to 1600 A)

mm

600×1400×2500

14

External dimensions (2000A–3150A)

mm

800×1600×2500

Consult now

Submit a message
Consult now