VS1 Series High-Voltage Vacuum Circuit Breaker

The VS1 (ZN63A) indoor high-voltage vacuum circuit breaker is switching equipment designed for 12 kV power systems, serving as the control and protection unit for electrical installations in industrial and mining enterprises, power plants, and substations. Owing to the inherent superior performance of vacuum circuit breakers, they are particularly well suited for applications requiring frequent operation at rated current or repeated interruption of short-circuit currents. This circuit breaker complies with the requirements of GB 1984-89 “Alternating-Current High-Voltage Circuit Breakers,” JB 3855-1996 “Indoor AC High-Voltage Vacuum Circuit Breakers, 3.6–40.5 kV,” and DL 403-2000 “Technical Specifications for Ordering High-Voltage Vacuum Circuit Breakers, 10–40.5 kV,” as well as the relevant requirements of IEC 56 (Publication 87).


Category:

Components

Keywords:

VS1 Series High-Voltage Vacuum Circuit Breaker



Detailed Introduction Technical Specifications

The VS1 (ZN63A) indoor high-voltage vacuum circuit breaker is switchgear designed for 12 kV power systems, serving as the control and protection device for electrical installations in industrial and mining enterprises, power plants, and substations. Owing to the inherent advantages of vacuum circuit breakers, they are particularly well suited for applications requiring frequent operation at rated current or repeated interruption of short-circuit currents. This circuit breaker complies with the requirements of GB 1984-89 “AC High-Voltage Circuit Breakers,” JB 3855-1996 “Indoor AC High-Voltage Vacuum Circuit Breakers, 3.6–40.5 kV,” and DL 403-2000 “Technical Specifications for Ordering 10–40.5 kV High-Voltage Vacuum Circuit Breakers,” as well as the relevant requirements of IEC 56 (publication No. 87). The circuit breaker features an integrated design that combines the operating mechanism with the breaker body, arranged in a front-to-back split configuration, and incorporates reliable interlocking functions. It can be installed as a fixed unit or mounted on a chassis to form a handcart unit.

Terms of Use:

Ambient temperature: +40℃ to -15℃ 
Ambient humidity: daily average relative humidity < 95% 
                    Daily average vapor pressure ≤ 2.2 × 10⁻⁵ MPa 
                    Monthly average relative humidity < 90% 
                    Monthly average vapor pressure: 1.8 × 10⁻³ MPa 
Altitude: ≤1000m 
Seismic intensity: <8 degrees 
The equipment shall be installed in locations free from dripping water, flammable and explosive hazards, corrosive chemical gases, and severe vibration.

Special Usage Conditions: If customers deviate from the normal operating conditions, they may negotiate with the manufacturer for custom manufacturing.

 

Technical Parameters of Circuit Breakers

Rated voltage12kV
Rated frequency50Hz
Rated lightning impulse withstand voltage (phase-to-phase, phase-to-ground) / interrupting gap(75) / 85 kV (peak)
Rated 1-min power-frequency withstand voltage (phase-to-phase, phase-to-ground) / interrupting gap(42) / 48 kV (RMS)
Rated Operating SequenceO-t-t-CO-t'-CO
Circuit breaker modelRated currentRated breaking current (kA)Rated short-circuit making current (peak) kARated short-circuit duration (s)Rated short-circuit current breaking operations (times)Mechanical Life (cycles)
VS1-12/...

630

1250

20/2550/63410020000

1250

1600

2000

2500

31.58045020000

1250

1600

2000

2500

3150

4010043010000

3150

4000

5012542010000