TANK1 Intelligent Universal Low-Voltage Vacuum Circuit Breaker
Category:
Components
Keywords:
TANK1 Intelligent Universal Low-Voltage Vacuum Circuit Breaker
The TANK1 series (intelligent) universal vacuum circuit breaker (hereinafter referred to as the “circuit breaker”) is suitable for AC distribution networks with a frequency of 50 Hz, rated voltages of 400 V and 690 V, and rated currents ranging from 630 A to 2000 A (the four-pole version is applicable to three-phase four-wire or three-phase five-wire systems). It is used for power distribution and for protecting circuits and power supply equipment against faults such as overloads, undervoltage, short circuits, and single-phase-to-ground faults.
The circuit breaker complies with standards such as GB 14048.2-2001 “Low-Voltage Switchgear and Controlgear—Low-Voltage Circuit Breakers” and IEC 60947-2 “Low-Voltage Switchgear and Controlgear—Low-Voltage Circuit Breakers.”
Features:
- High breaking capacity and strong arc-extinguishing capability, truly achieving zero arcing.
- It is particularly suitable for applications where air circuit breakers are either unsuitable or impractical, such as wind power generation, coal mining, chemical processing, and metallurgy.
- Circuit breakers are available in two structural configurations: fixed-type and drawer-type.
- Mechanical interlocks can be implemented in either the vertical or horizontal direction.
- It is interchangeable with the DW45-2000 main body designed by the Shanghai Institute of Electrical Engineering.
- The intelligent trip unit features four-stage protection with precise selective coordination.
- It can be equipped with an open communication interface and features four remote functions to meet the requirements of distribution automation systems.
- Passed the low-temperature resistance test at –40°C.
- Depending on the ambient air temperature, the intelligent trip unit can be selected as either digital or LCD type.
- Certified by 3C and holding national patent technology.
| Frame rating current Inm A | Rated current In A |
| 2000 | 630, 800, 1000, 1250, 1600, 2000 |
Rated short-circuit breaking capacity and short-time withstand current of circuit breakers
| Enclosure rating Rated current Inm(A) | 400V | 690V | ||||
| kA | ||||||
| Rated short-circuit limit Breaking capacity LCU | Rated short-circuit operation Breaking capacity lcs | Rated short-time withstand current Icw,1s delay 0.4s, O-CO | Rated short-circuit limit Breaking capacity Icu | Rated short-circuit operation Breaking capacity lcs | Rated short-time withstand current lcw.1s delay 0.4s, O-CO | |
| 2000 | 65 | 65 | 50 | 40 | 40 | 40 |
Operating Performance of Circuit Breakers
The operational performance of a circuit breaker is expressed in terms of the number of operation cycles.
| Frame rating current A | Number of power-on operation cycles | Number of operation cycles without power | Total |
| 2000 | 500 | 4500 | 5000 |
Contact Parameters of the Vacuum Arc-Extinguishing Chamber
| Name | Unit | Parameters |
| Opening distance | mm | 4±0.5 |
| Overrun | mm | ≥2.5 |