+
  • 110kV电力变压器.png

110 kV Power Transformer

The 110 kV power transformers developed and manufactured by Tian’an Electric are a series of products successfully brought to market through continuous exploration and refinement, based on the assimilation and application of advanced transformer manufacturing technologies both domestically and internationally, combined with the company’s own production experience. The reliability and performance specifications of these products have both reached the advanced domestic level.


Category:

Transformer

Keywords:

110 kV Power Transformer



Detailed Introduction Technical Specifications

The 110 kV power transformers developed and manufactured by Tian’an Electric are a series of products successfully brought to market through continuous exploration and refinement, based on the assimilation and integration of advanced transformer manufacturing technologies both domestically and internationally, combined with the company’s own production experience. The reliability and performance parameters of these products have all reached the leading domestic level. Notably, the three-phase, three-winding on-load tap-changing transformer passed its type tests in a single attempt in 2003, making Tian’an the first domestic manufacturer whose entire range of such transformers has been certified by the National Transformer Quality Supervision and Inspection Center. Through ongoing optimization and improvement, Tian’an has now established a comprehensive product line that includes 6,300–80,000 kVA two- and three-winding no-excitation tap-changing power transformers, as well as 6,300–80,000 kVA two- and three-winding on-load tap-changing power transformers.

Applicable to: Power plants, substations, and large industrial and mining enterprises.

 

1) Low losses: No-load losses are approximately 40% lower than those specified in the current national standard GB 6451, and load losses are approximately 15% lower than those specified in the same standard.
2) Low noise: Noise levels are below 60 dB, nearly 20 dB lower than the national standard, thereby meeting the power supply needs of urban grid residents in China.
3) Low partial discharge: Partial discharge level controlled below 100 pC;
4) Strong short-circuit withstand capability: The SZ-80000 kVA/110 kV transformer, independently designed and manufactured by our company, has successfully passed the short-circuit withstand capability test conducted by the National Transformer Quality Supervision and Inspection Center.
5) Aesthetic appearance: fuel tank with a folded-plate corrugated structure, shot-blasting rust removal, powder electrostatic spray coating, and wide-fin radiator—never fades.
6) Leak-proof: All sealing flanges are fully constrained, with double-seal construction on both the upper and lower box edges, and all sealing components are imported.

 

(S11 Series 110 kV Three-Phase Dual-Winding No-Excitation Voltage-Regulating Power Transformer)

Model

Voltage Combination and Tap Range

Connection Group

No-load loss 
(kW)

Load loss (kW)

No-load current 
(%)

Impedance Voltage 
(%)

High Voltage HV

Low Voltage LV

S(F)11-6300/110

110
115
121
±2×2.5%

6.3
6.6
10.5
11

Ynd11

7.4

34.2

0.45

10.5

S(F)11-8000/110

9.0

42.8

0.45

S(F)11-10000/110

10.6

50.4

0.44

S(F)11-12500/110

12.5

59.9

0.35

S(F)11-16000/110

15.0

73.2

0.3

S(F)11-20000/110

17.6

88.4

0.3

S(F)11-25000/110

20.8

104.5

0.3

S(F)11-31500/110

24.6

126.4

0.27

S(F)11-40000/110

29.4

148.2

0.27

S(F)11-50000/110

35.2

184.3

0.3

S(F)11-63000/110

41.6

222.3

0.3

S(F)11-75000/110

47.2

264.1

0.3

S(FP)11-75000/110

47.2

264.1

0.3

S(FP)11-80000/110

49.9

279.3

0.3

S(FP)11-90000/110

 

 

 

54.4

304.0

0.2

 

S(FP)11-150000/110

 

15.75

 

80.2

448.4

0.2

 

S(FP)11-240000/110

 

13.8

 

111.6

626.7

0.2

 

S11 Series 110 kV Three-Phase Dual-Winding On-Load Tap-Changing Power Transformer

Model

Voltage Combination and Tap Range

Connection Group

No-load loss 
(kW)

Load loss (kW)

No-load current 
(%)

Impedance Voltage 
(%)

High Voltage HV

Low Voltage LV

S(F)Z11-6300/110

110
±8×1.25%

6.3
6.6
10.5
11

Ynd11

8.0

34.2

0.35

10.5

S(F)Z11-8000/110

9.6

42.8

0.35

S(F)Z11-10000/110

11.4

50.4

0.35

S(F)Z11-12500/110

13.4

59.9

0.35

S(F)Z11-16000/110

16.2

73.2

0.3

S(F)Z11-20000/110

19.2

88.4

0.3

S(F)Z11-25000/110

22.7

104.5

0.3

S(F)Z11-31500/110

27.0

126.4

0.25

S(F)Z11-40000/110

32.3

148.2

0.2

S(F)Z11-50000/110

38.2

184.3

0.2

S(F)Z11-63000/110

45.4

222.3

0.2

S(FP)Z11-80000/110

49.9

279.3

0.2

Consult now

Submit a message
Consult now