  • XGN49-40.5(24)气体绝缘金属封闭开关设备(C-GIS).png

XGN49-40.5(24) Gas-Insulated Metal-Enclosed Switchgear (C-GIS)

The XGN49 series of indoor gas-insulated metal-enclosed switchgear (C-GIS), hereinafter referred to as the XGN49-40.5(24) gas-insulated cubicle, is a high-tech product independently developed by Tianan Electric. It employs vacuum arc-extinguishing and SF6 gas insulation technology, achieving a technical level that is domestically leading and internationally advanced.


Category:

Medium-Voltage Switchgear

Keywords:

XGN49-40.5(24) Gas-Insulated Metal-Enclosed Switchgear (C-GIS)



Detailed introduction Technical specifications

The XGN49 series of indoor gas-insulated metal-enclosed switchgear (C-GIS), hereinafter referred to as the XGN49-40.5(24) gas-insulated cubicle, is a high-tech product independently developed by Tianan Electric. It features vacuum arc-extinguishing technology and SF6 gas insulation, achieving a technical level that is domestically leading and internationally advanced.
The XGN49 inflatable switchgear features all high-voltage live components sealed within a stainless steel enclosure filled with SF6 gas at a lower pressure (0.03–0.05 MPa gauge, 20°C; rated IP67). The main switch uses a spring-operated vacuum circuit breaker equipped with a three-position isolating and earthing switch. The product boasts stable insulation performance and is particularly well-suited for harsh environments such as high altitudes, extreme cold, humidity, and pollution. Additionally, its compact footprint makes it ideal for space-constrained applications—such as rail transit systems—where land availability is limited.

 

1) Rated current can reach up to 3150A, with a short-circuit breaking capacity of 31.5kA;
2) External dimensions: 600 × 1400 × 2500 mm;
3) Employs vacuum arc extinction and SF6 gas insulation;
4) Through a high-altitude test at 5,000 meters;
5) The three-position isolating switch features a visible break.
6) The product is easy and quick to install—no on-site inflation required;
7) Overhead outgoing lines using tubular busbars can be employed;
8) A dual-busbar technical solution is achievable.

Serial Number

Project

Unit

Technical specifications

1

Rated current

A

630–3150

2

Rated frequency

Hz

50/60

3

Rated Voltage

kV

40.5 (24)

4

Rated Power Frequency Withstand Voltage

kV

95

5

Rated Lightning Impulse Withstand Voltage

kV

185

6

Rated Short-Circuit Interrupting Current

kA

20–31.5

7

Rated Short-Time Withstand Current (RMS) / Duration

kA/s

April 20 – April 31.5

8

Inflation-Shell Protection Rating

IP

67

9

Cabinet Protection Rating

IP

4X

10

SF6 gas rated operating pressure (gauge pressure at 20°C)

MPa

0.05

11

Minimum operating pressure of SF6 gas (gauge pressure at 20°C)

MPa

0.03

12

Annual Leakage Rate of SF6 Gas

%/year

≤0.5

13

External Dimensions (630A–1600A)

mm

600×1400×2500

14

External dimensions (2000A–3150A)

mm

800×1600×2500